KOREASCHOLAR

CFD 해석에 의한 대형선박 공기유입실의 급기팬 위치선정에 관한 연구 A Study on Selection of Supply Fan Location in Air Intake Room for Large Scaled Vessels by CFD Anal

조대환, 서광옥
  • 언어KOR
  • URLhttp://db.koreascholar.com/Article/Detail/291789
한국기계기술학회지 (韓國機械技術學會誌)
제16권 제1호 (2014.02)
pp.1155-1160
한국기계기술학회 (Korean Society of Mechanical Technology)
초록

For more efficient air-conditioning in large scaled vessels, structure of air inlet room and location of supply fan are very important. In this study, we have modeled an air intake room of large scaled vessels and tried to examine surrounding flow characteristics around supply fan by a numerical simulation using computational fluid dynamics based on three dimensional steady-state Navier-Stokes equation and standard k-ε model. A commercial CFD program, FLUENT, is used on the analysis. Finally, the analysis showed that the supply fan should be located at the inner side rather than outer side of air intake room, which was original design

목차
Abstract
 1. 서론
 2. 시뮬레이션
  2.1 모델링
  2.2 수치해석 방법
 3. 결과 및 고찰
 4. 결론
 References
저자
  • 조대환(목포해양대학교 기관시스템공학부) | Dae-Hwan Cho
  • 서광옥(목포해양대학교 대학원) | Seo-Kwang Oog