EES를 이용한 백연저감 열교환 시스템의 성능해석 연구 Study on Performance Analysis of White Smoke Reduction Heat Exchange System Using EES

왕쩐후안, 권영철
  • 언어KOR
  • URLhttp://db.koreascholar.com/Article/Detail/387302
한국기계기술학회지 (韓國機械技術學會誌)
제21권 제6호 (2019.12)
pp.1035-1040
한국기계기술학회 (Korean Society of Mechanical Technology)
초록

In this study, a white smoke reduction simple prediction model of white smoke reduction heat exchange system was developed by using EES. In order to verify the reliability of the EES model, it was compared with the computational results. The developed EES predictive model was used to calculate the temperature and absolute humidity of the mixed SA and EA according to the change of cooling water capacity, flow rate ratio of SA/EA, and SA inlet temperature. The difference between final temperature and absolute humidity at the outlet of the mixer calculated by computational analysis and EES was within 1.4% and 3.6%. As the cooling water capacity and the inlet flow rate ratio increased, and as the inlet air temperature decreased, the temperature and absolute humidity of the mixer decreased. The most influential factor in the white smoke reduction effect among the design variables of the white smoke reduction heat exchange system was the flow rate ratio of SA/EA.

목차
ABSTRACT
1. 서 론
2. 해석 방법
    2.1 전산해석 방법
    2.2 EES 모델
    2.3 EES 해석 방법 및 조건
    2.4 EES 계산 신뢰성 검증
3. 결과 및 고찰
4. 결 론
References
저자
  • 왕쩐후안(College of Electromechanical Engineering, Binzhou University) | Zhen-Huan Wang
  • 권영철(Dep. of Mech. Eng., Sunmoon University(Automation and Energy Technology Institute)) | Young-Chul Kwon Corresponding Author