KOREASCHOLAR

난방표준 온도조건에서 멀티 히트펌프의 운전특성에 대한 실험연구 Experimental Study on Operation Characteristics of Multi-H/P Under Heating Standard Temperature Condition

권영철
  • 언어KOR
  • URLhttp://db.koreascholar.com/Article/Detail/416640
한국기계기술학회지 (韓國機械技術學會誌)
제24권 제4호 (2022.08)
pp.555-560
한국기계기술학회 (Korean Society of Mechanical Technology)
초록

In the present study, it is conducted to understand the heating performance and compressor operation characteristics according to 7 indoor unit combinations and 3 setting temperatures of the inverter multi-heat pump under heating standard temperature conditions. Heating capacity, COP and compressor frequency are investigated using the multi-calorimeter. The indoor unit combinations are simultaneous operation(A+B+C), partial operation(A+C, A+B, B+C) and independent operation(A, B, C), and the setting temperature is 20, 21, and 30°C. Since the increase in the setting temperature increases the compress frequency, the heating capacity increases, but COP decreases due to the increase in power consumption. The frequency increases as the indoor unit combination capacity increases, and decreases as the setting temperature decreases in the steady state.

저자
  • 권영철(선문대학교) | Young Chul Kwon Corresponding author