In order to experimentally investigate the operation characteristics of the multi-heat pump with 3 indoor units, the dynamic characteristics of the cooling cycle is studied using the psychrometric multi-calorimeter. The compressor of the heat pump is the scroll inverter type, and since 3 indoor units operate cooling at the same time, it is operated at 100% full load. In particular, 3 types of indoor unit temperatures (20, 24, 26°C) are selected to understand the operation process of the multi-heat pump by the setting temperature. From this experiment, the compressor controls the EEV opening for each indoor unit while varying the frequency according to the initial start, transient, and steady operation. In addition, as the setting temperature increases in the steady range, the frequency of the compressor and the average opening degree of the EEV decrease.