KOREASCHOLAR

이동식 생물안전 연구시설 내 공조공기 급·배기구의 위치선정에 관한 해석적 연구 Analytical Study on Location of Supply and Exhaust Air in Mobile Biosafety Research Facility

김영득, 이주성
  • 언어KOR
  • URLhttp://db.koreascholar.com/Article/Detail/427128
한국기계기술학회지 (韓國機械技術學會誌)
제25권 제5호 (2023.10)
pp.816-821
한국기계기술학회 (Korean Society of Mechanical Technology)
초록

Recently a biosafety level-3(BL-3) mobile laboratory has been set up for the virus scanning and vaccine development because of the COVID-19 pandemic. The study on air flow inlet and outlet location and its flow direction with ventilation in the mobile laboratory needs to prevent spread of COVID-19 virus because the COVID-19 virus is primarily transmitted to people through respiratory droplets and aerosol coming out as their coughing. This study is conducted on the air flow pattern optimization in BL-3 mobile laboratory with various design specifications of position of air supply & exhaust port and particle source. Air flow patterns of ceiling supply-exhaust and ceiling supply-bottom side exhaust with particle source were determined to compare the impact of the infection prevention. CFD simulation was used to analyze for two air flow patterns and particle source position. Numerical results showed that air flow pattern of air conditioning system with ceiling supply-exhaust in a row is more effective than that of ceiling supply-bottom side exhaust air flow pattern in terms of infection prevention in biosafety mobile laboratory.

저자
  • 이주성(LG전자) | Joo-Seong Lee
  • 김영득(에너지환경협동조합) | Young-Deug Kim Corresponding author