초록

The seismic separation joint is an important device that absorbs vibration displacement from earthquake shock and protects fire extinguishing pipes and various utility pipes. In this study, the mechanical behavior occurring in U-typed and V-typed seismic separation joint was analyzed according to the length of the bellows, the length of the elbow straight pipe, and the open angle. As a result, as the length of the bellows increased, the stress and natural frequency decreased. In addition, as the length of the elbow straight pipe increased, the stress tended to decrease in the case of forced displacement in the vertical direction. As the open angle increased, the stress in the case of forced displacement in the left and right directions increased.

저자
  • 고병갑(Inha Technical College) | Byung-Kab Koh Corresponding author
  • 정혜리(CEO, Seung Jin Ind. Co., Gyeonggi-do, Korea) | Hye-Ri Jung
  • 박양섭(CEO, HB Tech, Gyeonggi-do, Korea) | Yang-Sub Park