KOREASCHOLAR

가변용량 공조시스템의 냉방성능에 대한 실험 연구 Experimental Study on Cooling Performance of Variable Capacity A/C System

권영철
  • 언어KOR
  • URLhttp://db.koreascholar.com/Article/Detail/435658
한국기계기술학회지 (韓國機械技術學會誌)
제26권 제2호 (2024.04)
pp.257-262
한국기계기술학회 (Korean Society of Mechanical Technology)
초록

In this study, the cooling performance of a variable capacity A/C system was experimentally studied. A psychrometric calorimeter was used to obtain performance data of the A/C system using the pulse width modulation method and compare it with the compressor discharge temperature correlation equation. Cooling capacity, COP, and compressor discharge temperature were obtained by changing indoor and outdoor temperatures, refrigerant amount, and loading duty. The following results were obtained by selecting 5 types of refrigerant amount, 3 types of outdoor temperature (fixed indoor temperature), and 2 types of loading duty. As the outdoor temperature increased, cooling capacity and COP according to outdoor conditions decreased. And the higher the loading duty, the greater the cooling capacity, but the COP was minimal. The change in cooling capacity and COP due to the increase in refrigerant amount was not significant. Additionally, the change in compressor discharge temperature is more influenced by the outside temperature than by the loading duty.

저자
  • 권영철(선문대학교) | Young Chul Kwon Corresponding author