KOREASCHOLAR

장배관 가변용량 공조시스템의 난방성능에 대한 실험 연구 Experimental study on heating performance of variable capacity A/C system with long pipes

권영철
  • 언어KOR
  • URLhttp://db.koreascholar.com/Article/Detail/435702
한국기계기술학회지 (韓國機械技術學會誌)
제26권 제3호 (2024.06)
pp.558-563
한국기계기술학회 (Korean Society of Mechanical Technology)
초록

In the present study, a calorimeter was used to experimentally investigate the heating capacity and COP changes according to the pipe length of a variable capacity A/C system with long pipes. Cooling capacity, COP, and compressor discharge temperature were obtained by changing pipe lengths and loading duties at fixed indoor and outdoor temperatures. And the operation status and cycle change process of the A/C system were investigated using some experimental data and P-h diagrams. As the pipe length changes, the heat transfer within the cycle and the operating load of the compressor change, so the heating capacity and COP of the system change. At the same loading duty, as the pipe length increases, the heating capacity and COP decrease. As the loading duty increased, the heating capacity increased almost linearly, but the COP decreased. Since the long pipe experimental value for the compressor discharge temperature has a temperature deviation of up to 1 7℃(50m, L/D : 10/10) from the correlation equation, the optimal correlation equation must be derived through additional research.

저자
  • 권영철(Department of Mechanical Engineering, Sunmoon University) | Young Chul Kwon Corresponding author