KOREASCHOLAR

가변형 공조시스템의 난방특성에 대한 실험 연구 Experimental Study on Heating Characteristics of Variable A/C System

이창수, 권영철
  • 언어KOR
  • URLhttp://db.koreascholar.com/Article/Detail/437787
한국기계기술학회지 (韓國機械技術學會誌)
제26권 제5호 (2024.10)
pp.1012-1017
한국기계기술학회 (Korean Society of Mechanical Technology)
초록

In this study, the calorimeter was used to experimentally investigate the heating characteristics of the variable A/C system according to changes in loading time and outdoor dry bulb temperature. The heating capacity, COP and compressor discharge temperature were measured while changing the loading time of the compressor. To develop the correlation for compressor discharge temperature, loading time, indoor dry bulb temperature and outdoor dry bulb temperatures were considered as operating variables. As the outdoor temperature and loading time increased, the heating capacity and COP increased. However, the change in COP showed different trends depending on the outdoor temperature. The evaporation temperature according to the loading time is a good estimate of the outdoor temperature. However, as the temperature difference between indoor and outdoor rooms decreases and the loading time increases, the condensation pressure increases significantly, so the condensation temperature increases. The maximum deviation between the correlation and the experimental value for compressor discharge temperature was within approximately 2℃.

목차
Abstract
1. 서 론
2. 실험방법 및 장치
3. 실험 결과
    3.1 공조시스템 난방 성능평가
    3.2 난방운전의 압축기 토출온도 상관식
4. 결 론
References
저자
  • 이창수(Department of Mechanical Engineering, Sunmoon University, Graduated student) | Changsoo Lee
  • 권영철(Department of Mechanical Engineering, Sunmoon University) | Young-Chul Kwon Corresponding author