환기설비가 설치된 교실의 실내 공기질 평가 KCI 등재후보

Indoor Air Quality Impact of Ventilation with the Existence of Occupants in Schools

  • 언어KOR
  • URLhttps://db.koreascholar.com/Article/Detail/31607
구독 기관 인증 시 무료 이용이 가능합니다. 4,000원
한국실내환경학회지 (Journal of Korean Society for Indoor Environment)
한국실내환경학회 (Korean Society for Indoor Environment)
초록

This paper describes to evaluate the performance of ventilation as a change of CO2 concentration with ventilation rate under 35 occupants in a school classroom. Variations of the CO2 concentration as a function of time are measured at center point of classroom with air ventilation rates by the CO2 gas monitor. For 800 m3/h of ventilation rate in the classroom, the average CO2 concentration is 913 ppm. The ventilation rate is sufficient to meet acceptable indoor air quality (≤ 1,000 ppm of CO2, KS school standard) in the classroom of 35 students.