논문 상세보기

10kW급 냉동유닛용 응축기의 성능특성에 대한 최적화 연구 KCI 등재

An Optimization Study of Performance Characteristics of Condenser for 10kW Refrigeration Unit

  • 언어KOR
  • URLhttps://db.koreascholar.com/Article/Detail/370694
구독 기관 인증 시 무료 이용이 가능합니다. 4,000원
한국기계기술학회지 (Journal of the Korean Society of Mechanical Technology)
한국기계기술학회 (Korean Society of Mechanical Technology)
초록

In this study, the cooling capacity and the pressure drop of a condenser for 10kW refrigerator unit were experimentally investigated. The performance characteristics of the condenser was studied by changing the fin shape(4 types), fin pitch(5 types), tube row(4 types) and air flow rate(6 types), using the calorimeter. The optimum heat exchanger specifications were selected by comparing the capacity and the pressure drop of the condenser. In order to select the heat exchanger suitable for the condenser for 10kW refrigerator unit, both the cooling capacity and the pressure drop should be considered. From the condenser performance test by pin type, the wavy pin was selected. The optimal performance of the condenser for 10kW refrigerator unit was observed at the fin pitch of 3 mm, the tube row of 4 row, and the air flow rate of 90㎥/min.

목차
ABSTRACT
 1. 서 론
 2. 실험장치 및 방법
 3. 실험 결과 및 고찰
  3.1 핀 형상에 따른 용량 및 압력강하
  3.2 핀 피치에 따른 용량 및 압력강하
  3.3 열수에 따른 용량 및 압력강하
  3.4 풍량에 따른 용량 및 압력강하
 4. 결 론
 References
저자
  • 최연성(Department of Mechanical Engineering, Sunmoon University, Graduated student) | Youn-Sung Choi
  • 권영철(Department of Mechanical Engineering, (Research Institute for Industrial Technology) Sunmoon University) | Young-Chul Kwon Corresponding Author