KOREASCHOLAR

PIV 풍동실험을 통한 대형공장 내부 풍환경 개선연구 Improvement of Wind Environment in a Large-scale Factory Building

이정엽, 장영길, Wei Zhang, 이상준
  • 언어KOR
  • URLhttps://db.koreascholar.com/Article/Detail/385237
한국풍공학회지
제9권 제2호 (2005.12)
pp.225-231
한국풍공학회 (Wind Engineering Institute of Korea)
초록

When air with high humidity is stagnant in a huge hot-rolling building, condensation occasionally occurs on the surface of hot-rolling steel coils, degrading quality of the products. To resolve this problem, we tried to utilize the natural ventilation effectively by modifying the location and size of opening vents based on quantitative visualization of ventilation flow inside the factory building. The 1/850 scale-down building model was embedded inside an atmospheric boundary layer simulated in a wind tunnel. The effects of wind direction and location of opening vents on the ventilation flow inside the factory building were investigated experimentally. Instantaneous velocity fields inside the building model were measured using a 2-frame PIV system. Among four dominant wind directions for the building tested, the condensation phenomena occurred monthly for the case of south wind. The addition of a vent on the southern wall of the factory building improved the natural ventilation effectively.

키워드
목차
Abstract
요 약
Ⅰ. 서 론
Ⅱ. 실험장치 및 방법
Ⅲ. 결과 및 토의
Ⅳ. 결 론
참고문헌
저자
  • 이정엽(포항공과대학교 기계공학과) | Lee Jung-Yeop
  • 장영길(포항공과대학교) | Jang Young-Gil
  • Wei Zhang(포항공과대학교 기계공학과)
  • 이상준(포항공과대학교 기계공학과) | Lee Sang-Joon