논문 상세보기

온실내 잉여열에너지 회수를 위한 팬코일 유닛시스템의 양액 가온효과 KCI 등재

Effect on Nutrient Heating of Fan Coil Unit System for Surplus Heat Recovery in Greenhouse

  • 언어KOR
  • URLhttps://db.koreascholar.com/Article/Detail/169120
구독 기관 인증 시 무료 이용이 가능합니다. 4,000원
한국기계기술학회지 (Journal of the Korean Society of Mechanical Technology)
한국기계기술학회 (Korean Society of Mechanical Technology)
초록

This study is nutrient heating effect to apply the surplus heat recovery in greenhouse using fan coil unit. Especially, this study was carried out to utilize a surplus heat in greenhouse. This fan coil unit system was composed of a water tank, a fan coil unit, a circulating pump and a water-water heat exchanger. As the result, Temperature difference duing to fan coil unit in greenhouse showed that air temperature at experimental greenhouse on fan , comparison greenhouse were 28.3℃, 33.9℃, respectively. heat ratio showed that exchanged energy quantity in fan coil unit was 19,900∼28,880kcal/h, respectively. It was found that difference of nutrient temperature due to surplus heat recovery, water tank temperature were 19.2∼21.5℃ and 16.2∼18.3℃, The temperature variation of nutrient temperature was about 3℃ and higher . Economic analysis of fan coil unit system was increased gross income cost by 804,787 won.

목차
Abstract
 1. 서론
 2. 재료 및 방법
 3. 결과 및 고찰
  3.1 팬코일 유닛 가동에 따른 온실내부의 온도변화
  3.2 팬코일 유닛의 가동에 따른 양액탱크내의 온도변화
  3.3 시간 및 온도차이에 따른 열교환량
  3.4 경제성 분석
 4. 요약 및 결론
 참고문헌
저자
  • 백이(농촌진흥청 시설원예시험장) | Y. PAEK
  • 전종길(농촌진흥청 시설원예시험장) | J. G. JEON
  • 윤남규(농촌진흥청 시설원예시험장) | N. K. YUN
  • 강금춘(농촌진흥청) | G. C. Kang
  • 이시영(농촌진흥청) | S. Y. LEE