In the study, space cooling performance of air source heat pump(ASHP) was evaluated in a pilot house. The ASHP, which provide for floor heating, domestic water heating and space cooling/heating, shows cooling capacity of 14.0 kW, when COP of ASHP was 3.21 based on test performance of KS C 9306. Test results shows that cooling capacity was depended on frequency of the compressor. The variable refrigerant flow rate for cooling were supplied into diverse room by using LEV. The COP at setting room temperature of 26℃ was 6.3% higher than the COP at that of 24℃, when the spending time in operation was decreased as 21.2%.