논문 상세보기

수경온실의 양액 냉각부하 예측모델 개발 KCI 등재

Development of a Numerical Model for Prediction of the Cooling Load of Nutrient Solution in Hydroponic Greenhouse

  • 언어KOR
  • URLhttps://db.koreascholar.com/Article/Detail/251897
구독 기관 인증 시 무료 이용이 가능합니다. 4,200원
생물환경조절학회지 (Journal of Bio-Environment Control)
한국생물환경조절학회 (The Korean Society For Bio-Environment Control)
초록

Cooling of nutrient solution is essential to improve the growth environment of crops in hydroponic culture during summer season in Korea. This study was carried out to provide fundamental data for development of the cooling system satisfying the required cooling load of nutrient solution in hydroponic greenhouse. A numerical model for prediction of the cooling load of nutrient solution in hydroponic greenhouse was developed, and the results by the model showed good agreements with those by experiments. Main factors effecting on cooling load were solar radiation and air temperature in weather data, and conductivity of planting board and area ratio of bed to floor in greenhouse parameters. Using the model developed, the design cooling load of nutrient solution in hydroponic greenhouse of 1,000m2(300pyong) was predicted to be 95,000 kJ/hr in Suwon and the vicinity.

저자
  • 남상운
  • 김문기
  • 손정익