논문 상세보기

해수냉각시스템 성능에 미치는 냉매배관길이의 영향 KCI 등재

Effect of Refrigerant Pipe Length on Sea Water Cooling System Performance

  • 언어KOR
  • URLhttps://db.koreascholar.com/Article/Detail/256228
구독 기관 인증 시 무료 이용이 가능합니다. 4,000원
수산해양기술연구 (Journal of the Korean Society of Fisheries and Ocean Technology)
한국수산해양기술학회(구 한국어업기술학회) (The Korean Society of Fisheriers and Ocean Technology)
초록

The purpose of this study is analyzing the performance of sea water cooling system under various refrigerant pipe length. In sea water cooling system, the increase of refrigerant pipe length cause increases of pressure drops. These pressure drops cause fresh gas in liquid pipe and increase specific volume in gas pipe outlet, so sea water cooling system capacity is decreased by decrease of refrigerant mass flow rate. Sea water cooling system capacity in refrigerant pipe length 70m is decreased more than 30% when compared with pipe length 10m and the decrease of the coefficient of performance is nearly 20%.

저자
  • 윤정인 | Yun, Jeong-In
  • 조영제 | Jo, Yeong-Je