논문 상세보기

고유황 보일러에서의 Sulfur Trioxide의 억제에 대한 연구 KCI 등재

Study on the Suppression of Sulfur Trioxide in High Sulfur Boiler

  • 언어KOR
  • URLhttps://db.koreascholar.com/Article/Detail/257893
구독 기관 인증 시 무료 이용이 가능합니다. 4,000원
한국응용과학기술학회지 (The Korean Society of Applied Science and Technology)
한국응용과학기술학회(구 한국유화학회) (The Korean Society of Applied Science and Technology (KSAST))
초록

The average sulfur content of crude oil is 2.2%. Coal is about 0.3 to 4.0 percent of the sulfur gases or particles being discharged into the atmosphere through the chimney as 1 to 2% SO3(Sulfur trioxide) and about 95% of the SO2 is reported. SO3 gas, which has many different causes of, as the combustion of sulfur containing fuel during the air due to the excess SO2 gas is oxidized to SO3 gas. Sulfur trioxide emitted from high sulfur heavy oil fired boiler caused white plume in stack and high temperature and cold end corrosion of facilities. So, in order to control sulfur trioxide concentration of Fuel gas in boiler, various of additives are used in other foreign. They are injected to Fuel Oil and consumed in boiler and reduce ash and the conversion rate of sulfur trioxide. In domestic, MgO compounds are used as additives but the total volume of them are made from other foreign company. In this study, MgO compounds were developed with liquid MgO compounds and field application was accomplished. The effect of newly developed chemicals and process were nearly equal to foreign products. In Consequent, the chemicals and process produced by newly developed technology can be substituted for foreign products and reduce the cost of plant operation.

저자
  • 최성부 | Choi, Sung-Bu