Mechanical Behavior of Slender Concrete-filled Fiber Reinforced Polymer Tubes

  • 언어ENG
  • URLhttps://db.koreascholar.com/Article/Detail/268802
구독 기관 인증 시 무료 이용이 가능합니다. 4,000원
리모델링 연구소 (A Journal of the Seismic Retrofitting & Remodeling Research Center)
단국대학교 리모델링연구소 (Seismic Retrofitting & Remodeling Research Center)
초록

The mechanical behavior of concrete-filled glass fiber reinforced polymer columns is affected by various factors including concrete strength, stiffness of tube, end confinement effect, and slenderness ratio of members. In this research the behavior of slender columns was examined both experimentally and analytically. Experimental works include 1) compression test with 30cm long glass fiber composite columns under different end confinement conditions, 2) uni-axial compression test for 7 slender columns, which have various slenderness ratios.Short-length stocky columns gave high strength and ductility revealing high confinement action of FRP tubes.The strength increment and strain change were examined under different end confinement conditions.With slender columns, failure strengths, confinement effects, and stress-strains relations were examined.Through analytical work, effective length was computed and it was compared with the amount of reduction in column strength, which is required to predict design strength with slender specimens.This study shows the feasibility of slender concrete-filled glass fiber reinforced polymer composite columns.

저자
  • Sok-Hwan Choi(Kookmin University)
  • Sung-Woo Lee(Kookmin University)
  • Myung Lee(Kookminci Composite Infrastructure, Inc.)