논문 상세보기

550MPa급 고강도 철근을 적용한 낮은 전단 벽체의 전단강도를 위한 반복가력 실험

Cyclic Tests for Shear Strength of Low-rise Shear Walls with 550MPa grade Re-bar

  • 언어KOR
  • URLhttps://db.koreascholar.com/Article/Detail/292532
서비스가 종료되어 열람이 제한될 수 있습니다.
한국구조물진단유지관리공학회 (The Korea Institute For Structural Maintenance and Inspection)
초록

In the construction of nuclear power plants using massive walls in Korea, the use of high-strength re-bars for shear design is necessary to enhance the constructability and economy. In the present study, low-rise walls(aspect ratio = 1.0) with 550MPa grade bars, were tested under cyclic loading to investigate shear capacity and deformation capacity of the walls. The results were compared with the performance of walls with grade 420 bars and predictions by current design code. The test results showed that ACI 349 underestimated the shear strength of the walls with 550 MPa grade bars. This result indicated that the ACI 349 predictions can be safely used for the earthquake design of the low-rise walls (aspect ratio =1.0) with 550 MPa grade bars.

저자
  • 백장운(서울대학교 건축학과 박사과정) | Baek, Jang Woon
  • 박홍근(서울대학교 건축학과 교수) | Park, Hong gun Corresponding Author