To predict the size of fire in the building, it was conducted a real fire experiment with a manufactured mock-up that had unit block size of 2.44 (L) × 3.6 (W) × 2.4 (H) m. The real fire testing was proceeded under scenario in which the fire starts from trash and is spread to all of real inflammable materials put beforehand inside the unit block such as bed, wardrobe and chest of drawers. As a experimental result, the fire grew rapidly about 120 seconds after the ignition, whose maximum heat release rate was 2658.9 kW.