열쾌적성과 국소환기지수를 고려한 에어컨 냉기 최적 토출각도에 대한 수치적 연구 KCI 등재후보

Numerical Study on the Optimal Discharge Angle of the 4-way Air Conditioner by Thermal Comfort and Local Ventilation Indices

  • 언어KOR
  • URLhttps://db.koreascholar.com/Article/Detail/31611
구독 기관 인증 시 무료 이용이 가능합니다. 4,000원
한국실내환경학회지 (Journal of Korean Society for Indoor Environment)
한국실내환경학회 (Korean Society for Indoor Environment)
초록

We performed numerical analyses on the optimal discharge angle of a 4-way cassette air conditioner, which is mounted on the ceiling of the classroom, by using thermal comfort and ventilation indices. We analyzed the effective draft temperature, the local mean age and the local mean residual life time with respect to the variation of the air discharge angle of the air conditioner in all occupied zone. Air diffusion performance index, local supply effectiveness and local exhaust effectiveness were used to investigate the optimal value of air discharge angle. From the results, we found out that the optimal discharge angle of the air conditioner is about 40 degrees in the present model.

저자
  • 노광철
  • 오명도