다중이용시설내 냉각탑수 및 실내공기에 존재하는 레지오넬라균 조사 KCI 등재후보

Investigation of L. pneumopila in Water Collected from Air Conditioning Cooling Towers and Indoor Air at Different Public Facilities

  • 언어KOR
  • URLhttps://db.koreascholar.com/Article/Detail/31617
구독 기관 인증 시 무료 이용이 가능합니다. 4,000원
한국실내환경학회지 (Journal of Korean Society for Indoor Environment)
한국실내환경학회 (Korean Society for Indoor Environment)
초록

This study was carried out to investigate the presence of L. pneumophila in indoor air and water collected from 692 air conditioning cooling towers at different public facilities. For these 4 years (2001~2004) of investigation, water samples were collected in high air conditioner operating month (from July to September) at department stores, hotels, offices, hospitals, discount stores, and public agencies. It was found that L. pneumophila was present in water samples from 47 air conditioning cooling towers. The detection rate of L. pneumophila was 7.6% in 2001, 10.7% in 2002, and 9.5% in 2003, respectively. When we compared the 4 air conditioner operating months, the highest rate of L. pneumophila detection was obtained in the water samples of July. The detection rate of L. pneumophila differed among different facilities. The highest detection rate of 17.9% was found in samples from department stores. L. pneumophila was detected similarly in water samples from hospitals (8.3%) and offices (8.2%). pH, temperature, and turbidity in the 47 L. pneumophila positive water samples ranged from pH 7 to 9, from 25℃ to 38℃, and from 1.0 to 3.5, respectively.

저자
  • 방선재
  • 박용배
  • 강정복
  • 김중범
  • 김종찬