경북도내 일부학교 교실의 실내공기질 평가 KCI 등재후보

A Survey on the Indoor Air Quality of Some School Classroom in Gyeongbuk area

  • 언어KOR
  • URLhttps://db.koreascholar.com/Article/Detail/31649
구독 기관 인증 시 무료 이용이 가능합니다. 4,000원
한국실내환경학회지 (Journal of Korean Society for Indoor Environment)
한국실내환경학회 (Korean Society for Indoor Environment)
초록

This study was performed to investigate the characteristics of indoor air quality (IAQ) in elementary and middle schools in Gyeongbuk area from July to November 2006 . The measurements of indoor air pollutants were made to cover such components as PM-10, CO2, CO, NO2, O3, HCHO, TVOC, TBC, and Radon from school classrooms. The results of this study can be summarized as follows: all of them were less than IAQ standards of Korea. The mean concentration were measured by 43.0 ㎍/㎥ (PM-10), 745 ppm (CO2), 56.1 ㎍/㎥ (HCHO), 350 CFU/㎥ (TBC), 0.026 ppm (O3), 0.6 ppm (CO), and 59.2 ㎍/㎥ (TVOC). Radon was not detected in all surveyed classrooms. The I/O ratio of PM-10 was 0.8∼1.4, while that for HCHO was 5.7∼9.0. Therefore, it was concluded that the indoor pollution of formaldehyde was very serious in classroom.