논문 상세보기

초저온 이원 냉동 시스템의 Cascade에서 과열도, 과냉각도 변화에 따른 온도 역전 현 상과 시스템 운전의 안정화에 대한 연구 KCI 등재

A Study on the Temperature Reversal Phenomenon and the Stabilization of System Operation in Cascade of Binary Refrigeration System with Superheat and Subcooling

  • 언어KOR
  • URLhttps://db.koreascholar.com/Article/Detail/364141
구독 기관 인증 시 무료 이용이 가능합니다. 4,000원
한국기계기술학회지 (Journal of the Korean Society of Mechanical Technology)
한국기계기술학회 (Korean Society of Mechanical Technology)
초록

This Study is carried out to stabilize the system according to the change of superheat and subcooling in binary refrigeration system by applying cascade system. When the system on 1 st stage was started and the system on the other side was operated, a temperature reversal phenomenon occurred in which the temperature of the 1 st cascade outlet was temporarily lowered. This means that the condensate heat exchange on the 2 nd is not good, which can cause the compressor to overheated. In order to maintain stable system operation, the opening degree of the expansion valve is controlled to increase the refrigerant circulation amount, thereby facilitating the condensation heat exchange on the 2 nd stage system. We have found that the most suitable refrigerant circulation amount is found by stabilizing the operation of the system while lowerning the super low temperature from -65℃ to -70℃ and increasing again to -60℃.

목차
ABSTRACT
 1. 서론
 2. 실험 장치 구성 및 수행
  2.1 실험 장치 구성
  2.2 실험 수행
 3. 실험 및 데이터 분석
  3.1 실험
 4. 결론 및 고찰
 References
저자
  • 백양선(Asan Campus of Korea Polytechnic) | Yang-Seon Baek Corresponding Author