In this study, the design of anchorage zone for unbonded post-tensioned concrete beam with single tendons of ultimate strength 2400MPa was evaluated to verify that the KDS 14 20 60(2016) and KHBDC 2010 codes are applicable. The experimental results showed that the bursting force equation of current design codes underestimated bursting stress measured by test, because the KDS 14 20 60(2016) and KHBDC 2010 propose the location of the maximum bursting force 0.5h which is the half of the height of member regardless of stress contribution. Although the allowable bearing force calculated by current design codes was not satisfied the prestressing force, the cracks and failure in anchorage zone was not observed due to the strengthening effect of anchorage zone reinforcement.