초록

In the present study, it is conducted to understand the heating performance and compressor operation characteristics according to 7 indoor unit combinations and 3 setting temperatures of the inverter multi-heat pump under heating standard temperature conditions. Heating capacity, COP and compressor frequency are investigated using the multi-calorimeter. The indoor unit combinations are simultaneous operation(A+B+C), partial operation(A+C, A+B, B+C) and independent operation(A, B, C), and the setting temperature is 20, 21, and 30°C. Since the increase in the setting temperature increases the compress frequency, the heating capacity increases, but COP decreases due to the increase in power consumption. The frequency increases as the indoor unit combination capacity increases, and decreases as the setting temperature decreases in the steady state.

저자
  • 권영철(선문대학교) | Young Chul Kwon Corresponding author