CFD Analysis of Thermal Response of Bridge Exposed to a Localized Pool Fire
This study presents a computational fluid dynamics (CFD) assessment of bridge thermal exposure to a localized pool fire. A four-phase procedure was used: infrastructure characterization, hazard definition and boundary conditions, virtual temperature monitoring, and simulation-based thermal assessment. The fire area was 1 m² and the prescribed heat release rate per unit area was 1,985 kW/m², corresponding to a nominal total heat release rate of 1.985 MW for a spatially uniform source. The simulation covered 3,600 s, with a vertical clearance of 6.6 m and a lateral standoff of 2.0 m. A maximum temperature of 132 °C was reported for the evaluated locations. The result represents the thermal response of the modeled case; it can‘t independently establish a minimum safe separation, the absence of concrete spalling, or post-fire structural capacity. Further validation and structural assessment are required before the results can support reopening decisions.