In this study, an externally reinforced structural system for SMC(Sheet Molding Compound) panel water tank, designed according to the Japanese design code, is experimented to evaluate its seismic performance. The test tank is 3m long, 2m wide and 3m high, considering the capacity and size of the shaking table. The measured hydrodynamic pressures are found to be approximately 70% of the Japanese design code values. It may be partially due to the convex shape effect of the unit panels. The analytical results of externally reinforced system based on the measured dynamic water pressures are found in good agreement with the test results. If the design hydrodynamic pressures are estimated properly, the proposed analytical model for the externally reinforced water tank becomes a useful design tool and the Japanese design code is found to provide a safe design for the external frames of SMC panel water tank.
본 연구에서는 전력, 통신 등 다양한 주요 기간설비의 운영에 필수적인 전기판넬의 내진성능개선을 위하여 내진보강시스템을 개발하고, 이 시스템의 내진성능평가를 위하여 진동대시험을 수행하였다. 본 연구에서 개발된 전기판넬 내진보강시스템은 이중바닥시스템(Access floor) 상에 설치된 전기판넬을 대상으로 운전하에서 무정전, 무이설 방식으로 내진보강이 가능하다는 장점을 지니고 있다. 진동대시험을 통해 전기판넬 내진보강시스템의 성능평가를 위하여 지진하중으로서 건물 내 여러 층에 설치되는 전기판넬의 특성을 고려하여 포괄응답스펙트럼을 입력하였다. 진동대시험은 널리 상용화되어 있는 스틸과 우드판넬 등 두 형식의 이중바닥시스템과 일반 전기판넬을 대표할 수 있는 동특성이 다른 두 종류의 전기판넬을 고려하여 총 4회 수행하였다. 진동대시험결과, 내진보강시스템은 진동대시험 중 및 후에도 전도 등으로 인한 전기판넬의 파손을 방지하는 등 전기판넬의 내진안전성을 확보하여 주는 것으로 나타났다. 따라서, 이중바닥시스템 상에 설치된 전기판넬에 개발된 내진보강시스템을 적용하는 경우, 지진으로 인한 전기판넬의 파손을 효과적으로 방지하여, 국내 주요 기간설비의 안정적 운영에 크게 기여할 수 있을 것으로 판단된다.
This study conducted seismic performance evaluation of externally reinforced water tank using shaking table test. From the shaking table test result, externally reinforced system shows sufficient stiffness for water tanks and high natural frequency over 8Hz. The test result also showed safety result of induced maximum stress of water tank shown in the allowable stress.