        1.
        2019.12 KCI 등재 구독 인증기관 무료, 개인회원 유료
        In this study, a white smoke reduction simple prediction model of white smoke reduction heat exchange system was developed by using EES. In order to verify the reliability of the EES model, it was compared with the computational results. The developed EES predictive model was used to calculate the temperature and absolute humidity of the mixed SA and EA according to the change of cooling water capacity, flow rate ratio of SA/EA, and SA inlet temperature. The difference between final temperature and absolute humidity at the outlet of the mixer calculated by computational analysis and EES was within 1.4% and 3.6%. As the cooling water capacity and the inlet flow rate ratio increased, and as the inlet air temperature decreased, the temperature and absolute humidity of the mixer decreased. The most influential factor in the white smoke reduction effect among the design variables of the white smoke reduction heat exchange system was the flow rate ratio of SA/EA.
        4,000원