        Heating and air conditioning system is changing rapidly from the traditional HVAC central supply system to the individual supply system with electrical heat pump system (EHP) in Korean school buildings. The individual supply system has advantages to turn on and off individually and to adjust the thermal comfort separately, but energy is wasted in the unoccupied classroom when the last leaving occupant does not turn off the controller. If the controller is to be off automatically while the classroom is not in use, energy consumption would decrease dramatically. This project aims to cease the unnecessary EHP supply in vacant classroom by inputting the class schedule from the central control room to reduce the energy-spending. Experimental measurements were carried out between the controlled classroom that is turned off when not in use and the uncontrolled room that is turned on continually. Occupant's comfort and energy consumption were measured and compared between the controlled case and the uncontrolled case. The energy consumption of controlled classroom case is 30-60% less than that of the uncontrolled classroom case. This result shows that controlling the cooling supply for the unoccupied classroom using the class schedule can decrease the energy consumption remarkably. This supply control system can be used to conserve energy in school structures like universities.