        검색결과 1

        1.
        2016.12 KCI 등재 구독 인증기관 무료, 개인회원 유료
        UPS system in the liquefied natural gas(LNG) receiving terminal is one of the fundamental equipment that need to sustain operation during earthquake. In this study, modal identification test of UPS system was performed based on IEEE Std. 693-2005 and natural frequencies and modal damping, mode shapes had been identified. In addition, tri-axial time history test was performed to check the behavior and stress of the equipment during earthquake. Eigenvalue analysis was performed and analysis model was modified by reflecting the results of the test. Static analysis by dead weight and response spectrum analysis were performed to compare the combined stresses with the stress results of test. Dynamic characteristics and combined stresses under seismic load condition of the improved analysis model were similar to the test results and in this regard the compatibility was proved.
        4,000원