논문 상세보기

지하수를 이용한 양액냉각시스템 개발에 관한 기초연구 KCI 등재

A Fundamental Study on the Nutrient Solution Cooling System Utilizing Ground Water

  • 언어KOR
  • URLhttps://db.koreascholar.com/Article/Detail/251886
구독 기관 인증 시 무료 이용이 가능합니다. 4,000원
생물환경조절학회지 (Journal of Bio-Environment Control)
한국생물환경조절학회 (The Korean Society For Bio-Environment Control)
초록

Experimental and theoretical analyses were carried out to investigate the heat exchange characteristics of the nutrient solution cooling system utilizing ground water. The material of heat exchanger used in the experiment was polyethylene and the cross-flow type was adapted in which nutrient solution was mixed and ground water unmixed. For the exchanger surface area of 0.33m2 and flow rates of ground water of 1-6l/min, NTU(number of transfer units) and effectiveness of experimental heat exchanger were 0.1-0.45 and 10-35%, respectively. Therefore these results showed that the hydroponic greenhouse of 1,000m2(300 pyong) with the ground water of 10m2/day could cover about 55-70% of maximum cooling load in summer.

저자
  • 남상운
  • 손정익
  • 김문기