In this study those currently operating SRF (Solid Refuse Fuel) combustion plant were selected for the investigation. The SRF component analysis, and the reaction time to collect contaminants collected and analyzed. As the result, the average caloric value of the SRF was about 8,114 kcal/kg and the result of the analysis was satisfied with the Fuel standard. The SRF could be used as an alternative Coal fuel. However CO, NOx and Dust analysis result was exceeded the emission standard. In case of Hydrogen chloride, high concentration of emission from the facilities was observed. Although normal operation was performed, ineffective the operational management causedt, incomplete blockage of drug injection facilities and personnel management system. To prevent such problems, a regular maintenance of facilities is need to be installed. At the moment applied to the monitoring system (TMS) are installed in waste incinerators with the medium to large capacities, However such as a periodically monitoring system is needed to manage a small solid fuel boliers as well.