CFD 해석에 의한 대형선박 공기유입실의 급기팬 위치선정에 관한 연구 KCI 등재

A Study on Selection of Supply Fan Location in Air Intake Room for Large Scaled Vessels by CFD Anal

  • 언어KOR
  • URLhttps://db.koreascholar.com/Article/Detail/291789
구독 기관 인증 시 무료 이용이 가능합니다. 4,000원
한국기계기술학회지 (Journal of the Korean Society of Mechanical Technology)
한국기계기술학회 (Korean Society of Mechanical Technology)
초록

For more efficient air-conditioning in large scaled vessels, structure of air inlet room and location of supply fan are very important. In this study, we have modeled an air intake room of large scaled vessels and tried to examine surrounding flow characteristics around supply fan by a numerical simulation using computational fluid dynamics based on three dimensional steady-state Navier-Stokes equation and standard k-ε model. A commercial CFD program, FLUENT, is used on the analysis. Finally, the analysis showed that the supply fan should be located at the inner side rather than outer side of air intake room, which was original design

목차
Abstract
 1. 서론
 2. 시뮬레이션
  2.1 모델링
  2.2 수치해석 방법
 3. 결과 및 고찰
 4. 결론
 References