개정 전단설계기준이 공동주택의 기초설계에 미치는 영향

The Effect of Isolated Footing Design on a Shear Design Article of KCI 2012 for Apartment

  • 언어KOR
  • URLhttps://db.koreascholar.com/Article/Detail/292602
서비스가 종료되어 열람이 제한될 수 있습니다.
한국구조물진단유지관리공학회 (The Korea Institute For Structural Maintenance and Inspection)
초록

This Paper evaluates the effect of Shear Design Article of KCI 2012 on the isolated footing of 15-story and 25-story frame type apartment buildings of which an apartment unit area is 59m2. As a result, the footing depth of a 15-story building shows 30.7% increase, and 25-story one, 39% increase, respectively. The minimum footing depth of isolated footing to resist pile punching is 750mm for a 15-story building and 830mm for a 25-story one.

저자
  • 이범식(LH공사 토지주택연구원 건설환경연구실 연구위원, 공학박사) | Lee, Bum Sik
  • 박성식(LH공사 토지주택연구원 건설환경연구실 수석연구원) | Park, Sung Sik