A study on Noise Generation and Awareness of the Fire Alarm Sound in the Factory
The people who are in the noise factory are difficult to hear and recognize about fire and to evacuate quickly when a fire occurs. This study was conducted to analyze workplace’s background noise of 31 factories in Incheon and to know the workplace noise level comparing to fire alarm sound level. The measured average noise level was 96.8dB(A). Noise level of measured result was exceeded as 6.8dB(A) comparing to NFSC (National Fire Safety Code) noise level of 90dB. NFPA suggests that when background noise exceeds 85dB or more than that, other methods should be considered to know alarm sound. Also fire alarm sound should exceed more than 15dB(A) comparing to background noise level. Therefore it was concluded that the design of the fire alarm systems should not be applied to the workplace without considering background noise and it needs to be improved with regulations and the systems.