공장소음으로 인한 화재 경보음 인지 영향정도에 관한 연구 KCI 등재

A study on Noise Generation and Awareness of the Fire Alarm Sound in the Factory

  • 언어KOR
  • URLhttps://db.koreascholar.com/Article/Detail/310702
구독 기관 인증 시 무료 이용이 가능합니다. 4,000원
대한안전경영과학회지 (Journal of Korea Safety Management & Science)
대한안전경영과학회 (Korea Safety Management & Science)
초록

The people who are in the noise factory are difficult to hear and recognize about fire and to evacuate quickly when a fire occurs. This study was conducted to analyze workplace’s background noise of 31 factories in Incheon and to know the workplace noise level comparing to fire alarm sound level. The measured average noise level was 96.8dB(A). Noise level of measured result was exceeded as 6.8dB(A) comparing to NFSC (National Fire Safety Code) noise level of 90dB. NFPA suggests that when background noise exceeds 85dB or more than that, other methods should be considered to know alarm sound. Also fire alarm sound should exceed more than 15dB(A) comparing to background noise level. Therefore it was concluded that the design of the fire alarm systems should not be applied to the workplace without considering background noise and it needs to be improved with regulations and the systems.

저자
  • 이영삼(세영 E&D 안전컨설팅 기술사사무소) | Lee, Young-Sam Corresponding Author