냉동유닛용 증발기의 공기측 열전달 및 압력강하에 대한 실험 연구 KCI 등재

An Experimental Study of Air-side Heat Transfer and Pressure Drop of Evaporator for Refrigerator Unit

  • 언어KOR
  • URLhttps://db.koreascholar.com/Article/Detail/367974
구독 기관 인증 시 무료 이용이 가능합니다. 4,000원
한국기계기술학회지 (Journal of the Korean Society of Mechanical Technology)
한국기계기술학회 (Korean Society of Mechanical Technology)
초록

In this study, the air-side cooling capacity and pressure drop of an evaporator for a refrigerator unit were experimentally investigated. Using the calorimeter, the performance of the evaporator was verified by changing the fin shape, fin pitch, tube row and air flow rate. The experimental apparatus consisted of the calorimeter which functioned as a constant temperature and humidity chamber and the refrigeration cycle. In order to select the heat exchanger suitable for the evaporator, both air-side cooling capacity and pressure drop should be considered at the same time. From the evaporator performance test by pin type, wavy pin was selected. The optimal performance of the evaporator was observed at the fin pitch of 5 mm, the tube row of 6 row, and the air flow rate of 40㎥/min.

목차
ABSTRACT
 1. 서 론
 2. 실험장치 및 방법
 3. 실험 결과 및 고찰
  3.1 핀 형상에 따른 냉방능력 및 압력강하
  3.2 핀 피치에 따른 냉방능력 및 압력강하
  3.3 열수에 따른 냉방능력 및 압력강하
  3.4 풍량에 따른 냉방능력 및 압력강하
 4. 결 론