In this study, the cooling and heating amount, temperature, flow rate of turbine type heat meter for water source heat-pump system were experimentally investigated at the standard operating conditions. The obtained cooling and heating capacity from the heat meter were deviated within 5.0%, 3.8% comparing with the precise values calculated from an accredited test facility. Even though the accumulated cooling and heating amount values of the heat meter had a small difference comparing with the precise values, the temperatures of heat meter showed greatly different values comparing with the precise temperature. Therefore, it is highly recommended to develop the heat meter which is appropriate for the water source heat pump systems.