논문 상세보기

에너지 절약을 위해 루프 열사이폰 열교환기를 적용한 컨테이너 냉방시스템의 냉방성능과 특성실험 KCI 등재

Experimental Study on the Cooling Performance and Characteristics of Container Cooling System using a Loop Thermosyphon Heat Exchanger for Energy Saving

  • 언어KOR
  • URLhttps://db.koreascholar.com/Article/Detail/417509
구독 기관 인증 시 무료 이용이 가능합니다. 4,000원
한국기계기술학회지 (Journal of the Korean Society of Mechanical Technology)
한국기계기술학회 (Korean Society of Mechanical Technology)
초록

Test of the operating characteristics and energy saving performance of a container cooling system that reduces the operating energy of a refrigeration system using a loop thermosyphon heat exchanger that removes heat by temperature difference between outdoor and indoor was performed. As a result of the experiments, when the loop thermosyphon and the refrigeration system were operated simultaneously, the refrigeration system operated intermittently by reducing the heat load. As the temperature difference between indoor and outdoor increased, the operating time of the refrigeration system decreased and the energy efficiency rate increased. Energy efficiency rate showed a tendency to increase with increasing temperature difference, and the predicted correlation of energy efficiency rate using the performance of the loop thermosyphon heat exchanger and the refrigeration system was relatively consistent with the experimental value.

저자
  • 강환국(동은 에이티에스) | Hwan-Kook Kang Corresponding author