논문 상세보기

소방용 지진 분리장치의 형상에 따른 기계적 거동 해석 KCI 등재

Analysis of Mechanical Behavior According to the Shape of Seismic Separation Joint for Fire Protection

  • 언어KOR
  • URLhttps://db.koreascholar.com/Article/Detail/432320
구독 기관 인증 시 무료 이용이 가능합니다. 4,000원
한국기계기술학회지 (Journal of the Korean Society of Mechanical Technology)
한국기계기술학회 (Korean Society of Mechanical Technology)
초록

The seismic separation joint is an important device that absorbs vibration displacement from earthquake shock and protects fire extinguishing pipes and various utility pipes. In this study, the mechanical behavior occurring in U-typed and V-typed seismic separation joint was analyzed according to the length of the bellows, the length of the elbow straight pipe, and the open angle. As a result, as the length of the bellows increased, the stress and natural frequency decreased. In addition, as the length of the elbow straight pipe increased, the stress tended to decrease in the case of forced displacement in the vertical direction. As the open angle increased, the stress in the case of forced displacement in the left and right directions increased.

저자
  • 고병갑(Inha Technical College) | Byung-Kab Koh Corresponding author
  • 정혜리(CEO, Seung Jin Ind. Co., Gyeonggi-do, Korea) | Hye-Ri Jung
  • 박양섭(CEO, HB Tech, Gyeonggi-do, Korea) | Yang-Sub Park