        2012.06 KCI 등재 구독 인증기관 무료, 개인회원 유료
        The thermal conductivity for the ground heat exchanger installed in the local facilities of greenhouse area at JangSu-Gun in Jeollabuk-Do was analyzed experimentally. For measuring the thermal conductivity of the ground heat exchanger, a bore hole was punched at the size of diameter 150mm, depth 160m. And a closed-type heat exchanger of high density polyethylene at the size of diameter 40mm was installed vertically. The heated water by an electric heater was circulated through the ground heat exchanger with a pump. The inlet/outlet temperatures and the flow rates of this water are measured and the thermal conductivity was calculated. The experimental results were as follows. The inlet/outlet temperatures of the ground heat exchanger were increased rapidly until 7 hours, then they were increased gently and the difference of inlet/outlet temperature was maintained at about 4.5℃. The thermal conductivity calculated by the line source theory was 2.207W/mK.
        4,000원
        3.
        2019.10 서비스 종료(열람 제한)
        다양한 리모델링 시공 중 추가적인 하중저항을 확보하기 위한 기초시공에서는 경제성, 시공성, 소음/진동 등의 이유로 헬리컬 파일을 사용하고 있으며, 좁은 공간에서 소규모 장비를 사용하여 회전관입하므로 파일의 길이가 3m로 제한되어 다수의 연결부가 소요된다. 이러한 연결을 위해 주로 가격이 낮은 pin 타입의 연결부가 사용되고 있으나 토크에 대한 저항력이 낮고 그라우팅이 어려운 단점을 가지고 있다. 이에 기존 대비 20% 이상 토크저항성을 가지며 동시에 경제성을 확보할 수 있는 새로운 헬리컬 파일 연결부를 고안하였고 유한요소해석을 통해 구조성능을 분석하였다.