        2015.10 KCI 등재 구독 인증기관 무료, 개인회원 유료
        Although disinfection in drinking water treatment plants provides a safer water supply by inactivating pathogenic microorganisms, harmful disinfection by-products may be formed. In this study, the disinfectant, chlorine, was produced on-site from the electrolysis of salt (NaCl), and the by-products of the disinfection process, bromate and chlorate, were analyzed. The provisional guideline levels for bromate and chlorate in drinking water are 10 μg/L and 700 μg/L, in Korea, respectively. Bromide salt was detected at concentrations ranging from 6.0 ~ 622 mg/kg. Bromate and chlorate were detected at concentrations ranging from non-detect (ND) ~ 45.3mg/L and 40.5 ~ 1,202 mg/L, respectively. When comparing the bromide concentration in the salt to the bromate concentration in the chlorine produced by salt electrolysis, the correlation of bromide to bromate concentration was 0.870 (active chlorine concentration from on-site production: 0.6–0.8%, n=40). The correlation of bromate concentration in the chlorine produced to that in the treated water was 0.866.