검색결과

검색조건
좁혀보기
검색필터
결과 내 재검색

간행물

    분야

      발행연도

      -

        검색결과 1

        1.
        2022.10 KCI 등재 구독 인증기관 무료, 개인회원 유료
        In the present study, to investigate the cooling characteristics of the multi-heat pump with 3 indoor units, 7 indoor unit combinations and 3 setting temperatures are selected to study the cooling characteristics during steady-state operation. The cooling capacity, power consumption, COP, compressor high and low pressure of the heat pump are tested under the cooling standard temperature conditions using an air enthalpy multi-calorimeter. The experimental results show that, except for an operation with an indoor unit capacity of 30% or less, the cooling capacity, power consumption, and compressor operation frequency increase as the capacity of the indoor unit increases and the setting temperature of the indoor unit decreases. COP increases or decreases according to the compressor frequency, and is the best at 50-80% capacity of the indoor unit. As the compressor frequency increases, the compressor outlet pressure increases by about 30%.
        4,200원