        2012.06 KCI 등재 구독 인증기관 무료, 개인회원 유료
        The thermal conductivity for the ground heat exchanger installed in the local facilities of greenhouse area at JangSu-Gun in Jeollabuk-Do was analyzed experimentally. For measuring the thermal conductivity of the ground heat exchanger, a bore hole was punched at the size of diameter 150mm, depth 160m. And a closed-type heat exchanger of high density polyethylene at the size of diameter 40mm was installed vertically. The heated water by an electric heater was circulated through the ground heat exchanger with a pump. The inlet/outlet temperatures and the flow rates of this water are measured and the thermal conductivity was calculated. The experimental results were as follows. The inlet/outlet temperatures of the ground heat exchanger were increased rapidly until 7 hours, then they were increased gently and the difference of inlet/outlet temperature was maintained at about 4.5℃. The thermal conductivity calculated by the line source theory was 2.207W/mK.