검색결과

검색조건
좁혀보기
검색필터
결과 내 재검색

간행물

    분야

      발행연도

      -

        검색결과 1

        1.
        2010.09 KCI 등재 구독 인증기관 무료, 개인회원 유료
        In this paper, cycle performance analysis of cascade refrigeration system using natural refrigerants R744 for low temperature cycle, and R290, R600, R600a, R717 for high temperature cycle are presented to offer the basic design data for the operating parameters of the system. The operating parameters considered in this study include subcooled and superheated degree, and condensing and evaporating temperature, temperature difference of cascade heat exchanger in cascade refrigeration system. The COP of cascade refrigeration system increases with the increasing subcooled degree, but there is no significant changes with the increasing superheated degree. The COP of cascade refrigeration system depends on evaporating and condensing temperatures of cascade heat exchanger. The COP of cascade refrigeration system using natural refrigerants is similar to the COP using freon refrigerant (R23 / R22). Points to be considered are th security, the attached facilities for natural refrigerants than COP.
        4,000원