        This study was conducted by survey and inspection of stair passage leading lights in shopping buildings which are more than 5 stories and have an underground parking lot located at Pyeongtaek-si and Seongnam-si. Number of shopping building for this study is 30 and of stair passage leading light inspected by two lights in each shopping building is 60. The result of this study is that the type of installed leading lights is LED(77%), and 60% of leading lights has problem such as no cleaning, scratch and discoloration, etc. The height of installed leading lights meets the fire law which is less than 1m from the floor. Visible condition of leading lights is good except some leading lights which have a little visible problem due to banner advertisement. 37% of standby power has flickered and went out. 93% of total leading lights meets the fire law which is more than 1lux from 0.5m distance, but cold cathode fluorescent lamps(CCFLs) have the problem which not meets proper brightness level based on fire law. In additional measurement result, zero lux of leading lights is 32%(from 1m distance), 68%(from 1.5m distance) and 98%(from 2m distance). Leading light is very important facility because it is eyes and guide when emergency. Therefore, proper fire facility operating function inspection and total detailed inspection are important to keep the good condition of leading light except simple visual check, and also improvement in law system of type approval, fire construction inspection and illumination level will be needed.