In the KEPIC-SNG, the domestic technical standard of the SC structure, the condition that the baseplate supporting the reinforcing bars is not bonded to the surface plate is suggested. However, if the baseplate is bonded only to the wingplate, all of the rebar loads generated on the baseplate will be transferred to the wingplate. The wingplate is expected to be conservatively designed in spacing and thickness to support the rebar load. In this study, the finite element analysis was carried out according to bonding conditions between surface plate and baseplate. As a result, it was confirmed that the overall structural strength was increased when the baseplate and the surface plate were bonded. Based on this result, it is possible to propose an economical design for the RC-SC connection such as increasing the wingplate spacing.