In this study, the flow characteristics at the front and the rear side of the diffuser installed in the AHU for Offshore HVAC system were studied. Set up the rectangular prism of which height is H at diffuser inlet duct, the flow control methods were considered using PIV and CFD numerical analysis. Average flow velocity was increased by 37% and the degree of flow uniformity was 96.7% at x/H =1.5.