The purpose of this study is to investigate the ELF-MF emissions from UCLs and to compare the ELF-MF emission levels of HVTLs and UCLs. In addition, this study proposes a method and management plan to investigate the effects of exposure to ELF-MF emissions from UCLs. The ELF-MF emissions from the 154 kV UCL were 15.4±24.4 (GM: 7.8)mG, while from the 345 kV line they were 6.0±2.4 (GM: 5.7)mG. Through the comparison between ELF-MF emissions of 154 kV UCL and HVTL, at about 20 m distance from an overhead line the emissions level is 4 mG, while from an underground line at about 10 m distance the emission level was recorded as less than 4 mG. Through comparing the ELF-MF emission amount of the UCL according to the burial method, it was found that the direct ELF-MF emission levels are 15.3±7.4 (GM: 13.9)mG at the direct point, in the conduit type 21.0±30.4 (GM: 10.8)mG, and in the buried form 8.5±12.3 (GM:5.1)mG. In this study, ELF-MF emissions were about 37.0% and 47.5% lower, respectively, compared with the direct power and conduit type. The correlation between ELF-MF emission (mG) and power load (A) was analyzed. The higher the power load, the higher the ELF-MF emission. The correlation between ELF-MF emission at the direct point and depth of the UCL was also analyzed, and it was found that as the depth of line burial increased, ELF-MF emissions decreased.