데이터 센터 및 건물 공조용 냉수코일의 종류에 따른 성능 특성에 관한 연구 KCI 등재

A Study on Performance Characteristics of Cooling Coil Type Used in Data Center or Building Air-Conditioning

  • 언어KOR
  • URLhttps://db.koreascholar.com/Article/Detail/387300
구독 기관 인증 시 무료 이용이 가능합니다. 4,000원
한국기계기술학회지 (Journal of the Korean Society of Mechanical Technology)
한국기계기술학회 (Korean Society of Mechanical Technology)
초록

In this study, heat exchangers used in data center and building air-conditioners were tested according to the type of heat exchangers to select them for commercial use. The experiment was performed three samples, one micro channel heat exchanger, the same volume oval coil and the same performance oval coil. The experiment conducted under actual operation conditions in the data center and building. Micro-channel heat exchanger has lower air side pressure drop and higher capacity per volume than oval coil. It may be advantageous when the installation small space or the little design static pressure in the fan, such as in-row systems or CRAC installed in data center.

목차
ABSTRACT
1. 서 론
2. 실험 조건 및 방법
3. 실험 결과 및 고찰
    3.1절 건표면 Cooling 조건에서 용량 및 압력손실 비교
    3.2절 습표면 Cooling 조건에서 용량 및 압력손실 비교
    3.3절 공기 유속에 따른 용량 및 공기측 압력손실 비교
    3.4절 물 유량에 따른 용량 및 공기측 압력손실 비교
4. 결 론